High Pressure Fluid Hammer Arrestors

HPC-500 - HPC-2000
Description:

Engineered to Tough PPP Standards
These units feature the same high quality design as our standard water hammer arrestors, with the exception of the seal rings and the addition of the high pressure filler cap at the top of the arrestor. The arrestors shown are rated for 2,000 PSI maximum spike operation.

Finished to Your Specifications
The expected spike pressure must be specified as well as the chemical make-up of the fluid in the system and the maximum temperature when ordering. Arrestors may be charged at the factory with either air or dry nitrogen per your specification. If arrestors are to be used in systems pumping volatile fluids, it is mandatory that they are charged with dry nitrogen.

 

Features:
  • High Pressure 2,000 PSI.
  • 600 lb Chrome Plated Liquid Filled Gauge.
  • U.S. Patent No.3,633.627
Application:
Adaptable to Your Individual Needs
Potable water, Industrial equipment using fresh water under high pressure. Available in NPT or BSP threads. Call factory for specific fluid application.
SPECIFICATIONS & INSTALLATION
CONSTRUCTION:
Brass Adapter, Type K copper barrel, Brass piston, High Pressure "O" rings, Brass Cap with ground seat filler valve.
CAP: Machined of free turning brass, attached to barrel
with 95-5 solder.
PISTON: Machined of Brass
SEALS: EPDM O-ring
SEAL LUBRICANT: Dow-Corning Silicone Compound #111, FDA listed for use in potable water systems.
OPERATING PRESSURE:

Normal operating pressure 0 to 150 PSI spike pressure not to exceed 2000 PSI.

TEMPERATURE: -40° F to + 212°  F (-4.4°  C to +100°  C)
INSTALLATION:
May be installed in new or existing plumbing systems with a standard pipe tee. No access panel required (Consult local code).
 
PART NUMBERS & SIZING CHART
 
PART NUMBER Size
HPC-500 1/2"
HPC-750 3/4"
 HPC-1000 1"
 HPC-1250 1"
 HPC-1500 1"
  HPC-2000  1"
      
       
 
Can't Find what you are looking for?
Please contact us at 503-328-6705 for TECHNICAL/SALES Support.