P-1 & P-2 Series Trap Primer Valve

P2-500 - P1-500
Description:

The Model P-1 & P-2 Trap Primer Valve is a precision device designed to deliver potable water to floor drains.

A pressure drop of 10 PSIG (70 Kpa) is required to activate the priming valve.

The Trap Primer must be installed on cold fresh water lines of 1 1/2" diameter or less.

The valves operating range is 20 to 80 PSIG (138 to 552 kpa).

 

Features:
  • Adjustable to line pressure
  • Piston operated, contains no springs or diaphragms
  • Easily adjusted to high or low pressures
Application:

Model P-1 will prime 1 to 4 floor drains using the PPP Patented distribution system

Model P-2 will prime 1 or 2 floor drains using the PPP Patented distribution system

SPECIFICATIONS & INSTALLATION
Construction: Machined from C69300 ECO Corrosion Resistant Brass.
Piston: Piston operated, contains no springs or diaphragms
Inlet: 1/2" NPT Male or
12mm BSP
Outlet:

1/2" NPT Female or

12mm BSP

Pressure: Easily adjusted to high or low pressures
INSTALLATION:

The priming valve must have a minimum elevation of 12 inches (305mm) above the finished floor.

Distribution Unit Installation:

Must Be Installed Level

Must Be Installed with Clear Plastic Cover

Must Be Installed with Access for Periodic Inspection

Do Not Subjetc Trap Primer Valve to Rough in Pressure Test

Please refer to the provided installation instructions when using our distribution units.

Caption
 
PART NUMBERS & SPECIFICATIONS
 
PART NUMBER # of Drains Distribution Unit
P2-500 1 N/A
P2-500 2 DU-4/DU-U
P1-500 3 DU-4/DU-U
P1-500 4 DU-4/DU-U
 

MULTIPLE DRAIN AND SINGLE DRAINP2 Trap Primer Diagram